Sounds like double ungood day for Linode
Sounds like double ungood day for Linode
Posted Jul 29, 2025 6:42 UTC (Tue) by MortenSickel (subscriber, #3238)In reply to: Sounds like double ungood day for Linode by bracher
Parent article: LWN is back
Just a couple of weeks before, we had done a system test and had the yearly service. It turned out there was some contamination in the cooling liquid that clogged the radiatior which was not detected in the service... The company doing the service got a few questions to answer, but as mentioned elsewhere here, the good thing is that we learned how to get the DC up from nothing.
Posted Jul 29, 2025 7:56 UTC (Tue)
by Wol (subscriber, #4433)
[Link] (1 responses)
The generator in this incident had a five minute header tank, which was re-filled by a pump from the main tank. Guess what the pump was plugged into ... the mains ...
Cheers,
Posted Jul 29, 2025 14:08 UTC (Tue)
by archaic (subscriber, #111970)
[Link]
Sounds like double ungood day for Linode
Wol
Sounds like double ungood day for Linode